1、室内气温低于20℃时,开启电加热器,对机器进行预热。
2、检查机体及周围有无妨碍运转的杂物,如有应及时清走。
3、检查曲轴箱油位、燃油箱油位、散热器水位。如油位水位低于规定值,应补充至正常位置。
4、检查燃油供油阀和冷却水截止阀是否处于开通位置。
5、检查柴油发电机组起动电动的蓄电池组电压是否正常。
6、检验配电屏的试验按钮,观察各报警指示灯有否接通发亮。
7、检查配电屏各开关是否置于分闸位置,各仪表指示是否处于零位。
8、启动进风和排风机。
9、按动发动机的起动按钮,使其启动运转。如第一次起动失败,可按下配电屏上相应的复位按钮,待其警报消除、发电机组回复正常状态方可进行第二次启动。启动后,机器运转声音正常,冷却水泵运转指示灯亮及路仪表指示正常,启动成功。
1. When the indoor temperature is below 20 ℃, turn on the electric heater to preheat the machine.
2. Check for any debris that may hinder the operation of the machine and its surroundings, and promptly remove them if found.
3. Check the crankcase oil level, fuel tank oil level, and radiator water level. If the oil level is lower than the specified value, it should be replenished to the normal position.
4. Check if the fuel supply valve and cooling water shut-off valve are in the open position.
5. Check if the voltage of the battery pack for starting the diesel generator set is normal.
6. Check the test button of the distribution panel and observe whether each alarm indicator light is turned on and on.
7. Check if all switches on the distribution panel are in the open position and if all instrument readings are in the zero position.
8. Start the intake and exhaust fans.
9. Press the start button of the engine to start and operate it. If the first start-up fails, the corresponding reset button on the distribution panel can be pressed, and the second start-up can only be carried out after the alarm is eliminated and the generator set returns to normal state. After starting, the sound of the machine running is normal, the indicator light for the cooling water pump running is on, and the road instrument reading is normal, indicating a successful start.